Specifications
- Cooling Capacity (kW): 5.1/5.6 @ Cold Water Temperature 22°C; Room Temperature 22°C Maximum Flow Range
- External Dimensions: 665x650x450mm
- Ambient Temperature Range: 20°C to 35°C
- Service Water Temperature Range: 20°C to 35°C
- Pressure: 0.39 MPa or Below
- Circulation Flow Range: 20 to 35 / 25 to 40 L/Min
- Water In & Outlet Connection Dia.: Rp 3/4
- Thermostat Differential: Setting Water Temperature: +/- 0.5
- Power Source: 3 Phase~ 200 +/-10% @ 50/60 Hz, 220 +/- 10% @ 60 Hz
- Power Consumption (kW): 1.4/1.7 @ 200V
- Current (Amps): 5.0/5.6 @ 200V
- Power Supply Capacity: 2.6 kVA
- Compressor Fully Enclosed, Rotary Type 1400
- Condenser: Finned Tube Style, Forced Air Cooling
- Heat Exchanger Structure: Shell & Coil Type
- Heat Exchanger Material: SUS304
- Fan Motor Output: 100 * 350
- Refrigeration Control Method: Capillary Tube
- Refrigerant: R407c
- Thermostat: Electric Type with Alarm Monitor
- Compressor Contains Internal Thermostat & Over Current Relay
- Refrigeration Circuit Contains High Pressure Switch & Defroster
- 6 Attached Drawings (3-CAA727, 3-CAA728, 4-CAA729, 3-CAA730, 3-CAA731, 4-CAA732)
- Minimum Water Volume: 120L (or More)
- Fan Flow Rate: 37/41 m³/Min (50/60 Hz)
- Typical Working Liquid Concentration Should Be Clean Water or a 30-40% Ethylene Glycol Solution
Replaces Old Orion Machinery Part Numbers
- There are no older part numbers.
Other Part Numbers
RKS-F-EDM Series, Orion, Light Duty Without Water Tank Chiller
Fits Models:
(Press ctrl + F to find model number below.)
RWC-20B